Power Line Systems, Inc. 610 N. Whitney Way, Suite 160
Madison, WI 53705, U.S.A.
Phone: (608) 238-2171, Fax: (608) 238-9241
Email: info@powline.com
Home Search News Products

AFL Telecommunications

OPGW wire files supplied by AFL Telecommunications. There are four types of OPGW models available:

AlumaCore (view catalog page)

FIBERS (max) OPGW SIZE FAULT CURRENT TOTAL CONDUCTOR AREA TOTAL CONDUCTOR AREA OVERALL DIAMETER OVERALL DIAMETER WEIGHT WEIGHT RBS RBS
(kA)˛sec in˛ mm˛ in mm lbs/ft kg/m lbs kg
8 AC-53/449 39 0.1166 75.24 0.449 11.4 0.282 0.42 15122 6860
8 AC-27/27/449 48 0.1166 75.24 0.449 11.4 0.211 0.315 9679 4390
8 AC-86/535 74 0.1677 108.17 0.535 13.6 0.43 0.64 22879 10378
8 AC-43/43/535 96 0.1677 108.17 0.535 13.6 0.315 0.469 14539 6595
12 AC-57/465 41 0.121 78.08 0.465 11.8 0.3 0.447 16214 7355
12 AC-29/29/465 51 0.121 78.08 0.465 11.8 0.224 0.333 10344 4692
12 AC-72/504 56 0.1445 93.21 0.504 12.8 0.368 0.548 20329 9221
12 AC-32/40/504 70 0.1445 93.21 0.504 12.8 0.282 0.42 13732 6229
24 AC-64/528 68 0.151 97.43 0.528 13.4 0.359 0.535 18391 8342
24 AC-29/34/528 81 0.151 97.43 0.528 13.4 0.281 0.418 12351 5602
24 AC-74/552 81 0.1666 107.51 0.552 14 0.405 0.602 21132 9585
24 AC-37/37/552 98 0.1666 107.51 0.552 14 0.306 0.455 13556 6149
36 AC-71/571 95 0.1758 113.39 0.571 14.5 0.411 0.611 20546 9320
36 AC-33/38/571 110 0.1758 113.39 0.571 14.5 0.323 0.48 13779 6250
36 AC-86/607 118 0.2002 129.14 0.607 15.4 0.481 0.716 24829 11263
36 AC-40/47/607 141 0.2002 129.14 0.607 15.4 0.375 0.558 16646 7551
48 AC-86/646 151 0.2208 142.43 0.646 16.4 0.509 0.757 25098 11384
48 AC-34/52/646 172 0.2208 142.43 0.646 16.4 0.417 0.621 18053 8189
48 AC-129/724 239 0.2876 185.57 0.724 18.4 0.703 1.046 35034 15891
48 AC-65/65/724 292 0.2876 185.57 0.724 18.4 0.53 0.789 22524 10217
72 AC-88/659 154 0.2232 143.98 0.659 16.7 0.516 0.768 25556 11592
72 AC-38/49/659 177 0.2232 143.98 0.659 16.7 0.414 0.615 17698 8028
72 AC-102/691 182 0.246 158.96 0.691 17.5 0.582 0.866 29555 13406
72 AC-44/58/691 212 0.246 158.96 0.691 17.5 0.465 0.692 20566 9329
144 AC-82/646 144 0.2147 138.52 0.646 16.4 0.395 0.588 24,069 10,918
144 AC-39/43/646 166 0.2147 138.52 0.646 16.4 0.498 0.741 16,145 7,323
144 AC-125/726 230 0.2813 181.48 0.726 18.4 0.6919 1.030 34,882 15,823
144 AC-58/67/726 277 0.2813 181.48 0.726 18.4 0.5378 0.800 23,286 10,562

HexaCore (view catalog page)

FIBERS (max) OPGW SIZE FAULT CURRENT TOTAL CONDUCTOR AREA TOTAL CONDUCTOR AREA OVERALL DIAMETER OVERALL DIAMETER WEIGHT WEIGHT RBS RBS
(kA)˛sec in˛ mm˛ in mm lbs/ft kg/m lbs kg
24 SX-32/45/472 41 0.1235 79.67 0.472 12 0.281 0.418 14,947 6,780
36 SX-41/32/472 41 0.1186 76.53 0.472 12 0.247 0.368 12,122 5,498
24 SX-75/37/555 96 0.1757 113.37 0.555 14.1 0.317 0.471 15,392 6,982
24 SX-90/30/575 116 0.1889 121.86 0.575 14.6 0.313 0.466 14,464 6,561
96 S1-82/52/630 137 0.2131 137.45 0.63 16 0.417 0.621 20,042 9,091
96 S1-83/59/647 152 0.2265 146.13 0.647 16.4 0.453 0.674 22,131 10,039
96 S1-91/61/668 177 0.2429 156.69 0.668 17 0.479 0.712 23,302 10,570
144 S1-71/52/630 118 0.2006 129.41 0.63 16 0.41 0.61 19,791 8,977
144 S1-73/59/647 132 0.214 138.09 0.647 16.4 0.452 0.673 21,880 9,925
144 S1-81/61/668 155 0.2304 148.65 0.668 17 0.472 0.702 23,051 10,456
216 S1-61/52/630 100 0.1881 121.37 0.63 16 0.416 0.619 19,540 8,863
216 S1-63/59/647 114 0.2016 130.05 0.647 16.4 0.451 0.672 21,630 9,811
216 S1-71/61/668 135 0.2179 140.6 0.668 17 0.477 0.71 22,801 10,342
288 S1-41/52/630 68 0.1632 105.28 0.63 16 0.414 0.616 19,038 8,636
288 S1-42/59/647 79 0.1766 113.96 0.647 16.4 0.45 0.67 21,128 9,584
288 S1-50/61/668 97 0.193 124.52 0.668 17 0.476 0.708 22,299 10,115

CentraCore (view catalog page)

AFL updated the CC-75/528 48F wire file on May 2nd, 2011.

FIBERS (max) OPGW SIZE FAULT CURRENT TOTAL CONDUCTOR AREA TOTAL CONDUCTOR AREA OVERALL DIAMETER OVERALL DIAMETER WEIGHT WEIGHT RBS RBS
(kA)˛sec in˛ mm˛ in mm lbs/ft kg/m lbs kg
48 CC-57/465 43 0.1248 80.52 0.465 11.8 0.314 0.467 16,626 7,541
48 CC-29/29/465 54 0.1248 80.52 0.465 11.8 0.238 0.354 10,755 4,878
48 CC-54/472 53 0.1339 86.39 0.472 12 0.317 0.471 16,089 7,298
48 CC-27/27/472 63 0.1339 86.39 0.472 12 0.244 0.364 10,523 4,773
48 CC-63/496 63 0.1474 95.08 0.496 12.6 0.356 0.529 18,454 8,371
48 CC-29/34/496 75 0.1474 95.08 0.496 12.6 0.28 0.416 12,584 5,708
48 CC-72/504 58 0.1482 95.64 0.504 12.8 0.382 0.568 20,740 9,408
48 CC-32/40/504 74 0.1482 95.64 0.504 12.8 0.296 0.441 14,144 6,416
48 CC-75/528 75 0.1646 106.2 0.528 13.4 0.41 0.611 21,831 9,903
48 CC-38/38/528 94 0.1646 106.2 0.528 13.4 0.31 0.461 14,092 6,392
72 CC-54/472 51 0.1318 85.01 0.472 12 0.316 0.47 16,067 7,288
72 CC-27/27/472 61 0.1318 85.01 0.472 12 0.243 0.362 10,501 4,763
72 CC-63/496 60 0.1452 93.7 0.496 12.6 0.355 0.528 18,432 8,361
72 CC-29/34/496 73 0.1452 93.7 0.496 12.6 0.278 0.414 12,561 5,698
72 CC-63/507 71 0.1547 99.8 0.507 12.9 0.367 0.546 18,677 8,472
72 CC-32/32/507 85 0.1547 99.8 0.507 12.9 0.282 0.42 12,195 5,532
72 CC-75/528 75 0.1646 106.2 0.528 13.4 0.41 0.611 21,831 9,903
72 CC-38/38/528 94 0.1646 106.2 0.528 13.4 0.31 0.461 14,092 6,392
72 CC-73/532 84 0.1701 109.73 0.532 13.5 0.411 0.612 21,380 9,698
72 CC-33/40/532 100 0.1701 109.73 0.532 13.5 0.323 0.48 14,561 6,605

Renewables Optimized OPGW CentraCore (view catalog page)

FIBERS (max) OPGW SIZE FAULT CURRENT TOTAL CONDUCTOR AREA TOTAL CONDUCTOR AREA OVERALL DIAMETER OVERALL DIAMETER WEIGHT WEIGHT RBS RBS
(kA)˛sec in˛ mm˛ in mm lbs/ft kg/m lbs kg
48 CC-52/461 47 0.1265 81.62 0.461 11.70 0.302 0.450 15,403 6,987
48 CC-26/26/461 56 0.1265 81.62 0.461 11.70 0.233 0.346 10,066 4,566
48 CC-54/465 49 0.1300 83.86 0.465 11.80 0.312 0.464 16,012 7,263
48 CC-27/27/465 59 0.1300 83.86 0.465 11.80 0.240 0.357 10,446 4,738
48 CC-61/484 56 0.1399 90.25 0.484 12.30 0.341 0.508 17,748 8,051
48 CC-28/33/484 67 0.1399 90.25 0.484 12.30 0.268 0.398 12,093 5,485
48 CC-70/512 67 0.1554 100.26 0.512 13.00 0.385 0.573 20,473 9,286
48 CC-35/35/512 84 0.1554 100.26 0.512 13.00 0.291 0.433 13,225 5,999
48 CC-87/551 88 0.1801 116.17 0.551 14.00 0.457 0.680 24,195 10,975
48 CC-38-48-551 109 0.1801 116.17 0.551 14.00 0.355 0.528 16,464 7,468
48 CC-89/555 91 0.1839 118.66 0.555 14.10 0.468 0.696 24,856 11,275
48 CC-40/49/555 114 0.1839 118.66 0.555 14.10 0.363 0.539 16,902 7,667

SlottedCore (view catalog page)

FIBERS (max) OPGW SIZE FAULT CURRENT TOTAL CONDUCTOR AREA TOTAL CONDUCTOR AREA OVERALL DIAMETER OVERALL DIAMETER WEIGHT WEIGHT RBS RBS
(kA)˛sec in˛ mm˛ in mm lbs/ft kg/m lbs kg
36 SC-43/44/502 64 0.1347 86.91 0.504 12.8 0.289 0.430 12910 5856
48 SC-38/62/537 80 0.1561 100.71 0.535 13.6 0.366 0.544 17436 7909
48 SC-38/69/553 89 0.1661 107.17 0.551 14.0 0.394 0.587 19178 8699
72 SC-37/64/558 78 0.1555 100.33 0.559 14.2 0.376 0.559 17767 8059
48 SC-38/88/596 118 0.1955 126.12 0.594 15.1 0.480 0.714 24332 11037
96 SC-47/72/613 111 0.1838 118.60 0.614 15.6 0.439 0.653 20060 9099
144 SC-65/62/643 136 0.1960 126.42 0.642 16.3 0.433 0.644 18115 8217
144 SC-66/66/655 149 0.2058 132.75 0.654 16.6 0.457 0.680 19504 8847
144 SC-54/79/655 141 0.2058 132.75 0.654 16.6 0.491 0.730 22149 10047
96 SC-69/80/676 183 0.2314 149.32 0.677 17.2 0.517 0.770 23761 10778
96 SC-47/102/676 168 0.2314 149.32 0.677 17.2 0.576 0.857 28426 12894
144 SC-76/88/714 220 0.2533 163.40 0.713 18.1 0.570 0.848 25833 11718
144 SC-54/110/714 202 0.2533 163.40 0.713 18.1 0.628 0.935 30487 13829
72 SC-124/64/735 317 0.2911 187.80 0.736 18.7 0.537 0.799 22992 10429
96 SC-142/72/790 413 0.3317 214.03 0.791 20.1 0.616 0.916 25758 11684
96 SC-165/102/873 627 0.4141 267.13 0.874 22.2 0.792 1.179 35452 16081
96 SC-193/102/916 780 0.4579 295.44 0.917 23.3 0.845 1.258 37143 16848
144 SC-207/110/954 899 0.4911 316.83 0.953 24.2 0.910 1.354 39652 17986

© 2008 Power Line Systems, Inc. All Rights Reserved.